Hi,

we get a new SNMP-Adapter(CS121) in our AEG-USV Protect 3.33. Now is the question how can i import the information from this SNMP-Adapter to PRTG?

Did anyone try this before? Are there any code to use?


Article Comments

Hello Max-bfm,

Thank you for your question.

I assume you are referring to the GENEREX USV-Adapter CS121

If this is correct, please download the related MIB-File RFC1628cs121.MIB and use our MIB-Importer to generate an OIDlib-file which should be saved under C:\Program Files (x86)\PRTG Network Monitor\snmplibs.

Once you have done this, you can monitor the target with the "SNMP Library Sensor"

Here's a KB-article that describes the setup of "SNMP Library Sensors" and there's also a video that shows how to.

Please let us know, if you have any further questions.

Kind regards, Sven


Nov, 2016 - Permalink

Hi Sven,

thanks for your answer. I solve my problem with a PRTG "snmpcustomsensor" an the OID.

It works with: OID: 1.3.6.1.2.1.33.1.2.3 - Remaining Minutes OID: .1.3.6.1.2.1.33.1.2.4.0 - Battery Capacity

Best regards, Max


Nov, 2016 - Permalink